Sensor Types
                                
                                
                                    4 to 20 mA with or without HART, 0 to 20 mA
                                
                             
                            
                                
                                    Nominal Signal Range (span)
                                
                                
                                    4 to 20 mA, (0 to 20 mA option)
                                
                             
                            
                                
                                    Full Signal Range
                                
                                
                                    0 to 24 mA
                                
                             
                            
                                
                                    Accuracy over temperature range
                                
                                
                                    0.25% of span (0 to 60°C), 0.5% of span (-40 to 70°C)
                                
                             
                            
                                
                                    Resolution
                                
                                
                                    16 bit D/A converter
                                
                             
                            
                                
                                    Calibration
                                
                                
                                    None Required
                                
                             
                            
                                
                                    Avaliable Field Power
                                
                                
                                    20 mA at 15 V DC supply into 750 Ω load
                                
                             
                            
                                
                                    Field Circuit Protection
                                
                                
                                    24 mA Current Limiting Circuit, Field wiring disconnect
                                
                             
                            
                                
                                    CHARM Power req.
                                
                                
                                    42 mA max @ 24 V DC
                                
                             
                            
                                
                                    CHARM Heat Dissipation
                                
                                
                                    0.48 W
                                
                             
                            
                                
                                    HART Support
                                
                                
                                    HART v7 pass-through for AMS, HART v7 variable and device status available to control
                                
                             
                            
                                
                                    HART Data Update Rates
                                
                                
                                    Update rates are faster than every second dependent on HART communication loading and device type